Tornatech - Fire Pump Controllers - Industrial Pump Controllers - Toll Free : 1-800-363-8448

Jockey Pump Controllers


Model DJD

Model DJD

Jockey Pump Controllers

UL CE CSA

Controller protection level:

  • Standard: NEMA - UL - CSA type 3, and 3R
  • Optional: NEMA - UL - CSA type 12 or 4 or 4X

Operational temperature limits:

  • 41°F to 122°F (5°C to 50°C)

Short circuit interrupting capacity:

  • 65 KA (RMS) at 120 V. to 240 V.
  • 25 KA (RMS) at 380 V. to 480 V.
  • 18 KA (RMS) at 600 V.

Manual operators (door mounted):

  • Two circuit breaker handles door interlocked c/w padlock provision in OFF position
  • One "Hand-Off-Auto" selector switch, rotary type, heavy duty
  • One "P1-AUTO-P2" lead pump selector switch, rotary type, heavy duty
  • One "Normal-Test" selector switch, rotary type, heavy duty.

Control features:

  • Two molded case circuit breakers (MCP)
  • Two motor contractors HP rated
  • One motor overload relays
  • One pressure switch for clean water only c/w adjustable cut-in setting and independent differential adjustment (6-250PSIG).
  • Two control transformers (line voltage to 120V.)
  • One automatic switchover device including voltage & frequency sensing circuit board and transformers
  • One "Power on" pilot light
  • One "Power on" pilot light
  • Two "Run" pilot light
  • One "Alternate power" pilot light
  • One "Normal power" pilot light
  • One "Connected to Normal position" pilot light
  • One "Connected to Alternate position" pilot light

How to order:

DJD-V/HP/Ph/Hz
DJD-208/2 x 2/3/60
Brochure
Submittal drawings


Tornatech
7075, Place Robert-Joncas # 132
Saint-Laurent (Québec)
H4M 2Z2

Printed on: Thursday, July 29, 2010
Phone: 514 334–0523
Fax: 514 334-5448
Toll free: 1 800 363-8448
E-mail: info@tornatech.com