Controller protection level:
- Standard: NEMA 2
- Optional: NEMA 12 or 4 or 4X or 3/3R
Operational temperature limits:
- 41°F to 122°F (5°C to 50°C)
Short circuit interrupting capacity:
- 65 KA (RMS) at 120 V. to 240 V.
- 25 KA (RMS) at 380 V. to 480 V.
- 18 KA (RMS) at 600 V.
Manual operators (door mounted):
- Two circuit breaker handles door interlocked c/w padlock provision in OFF position
- One "Hand-Off-Auto" selector switch, rotary type, heavy duty
- One "P1-AUTO-P2" lead pump selector switch, rotary type, heavy duty
- One "Normal-Test" selector switch, rotary type, heavy duty.
Control features:
- Two molded case circuit breakers (MCP)
- Two motor contractors HP rated
- One motor overload relays
- One pressure switch for clean water only c/w adjustable cut-in setting and independent differential adjustment (6-250PSIG).
- Two control transformers (line voltage to 120V.)
- One automatic switchover device including voltage & frequency sensing circuit board and transformers
- One "Power on" pilot light
- One "Power on" pilot light
- Two "Run" pilot light
- One "Alternate power" pilot light
- One "Normal power" pilot light
- One "Connected to Normal position" pilot light
- One "Connected to Alternate position" pilot light
How to order:
| DJD- | V/ | HP/ | Ph/ | Hz |
| DJD- |
208/ |
2 x 2/ |
3/ |
60 |
Brochure
Submittal drawings