Standard
• Micro-processor based logic control
• Two independent fully automatic battery chargers for 12 VDC or 24 VDC rated at 10 A.
• Automatic starting of engine on pressure drop as detected by a built-in 304 stainless steel pressure transducer rated for 0-300 PSI
• Manual starting of engine by manual crank pushbuttons
• Programmable time clock for Weekly Test and manual Run Test push button initiated by energizing of drain solenoid valve Manual and Automatic stop (programmable minimum run period timer)
• Sequential start timer (programmable)
• Automatic crank cycle as per NFPA 20
• Visual alarms as per NFPA 20
• 4’’ alarm bell
• AC and DC circuit breakers Master selector switch (Hand-Off-Auto)
• Provision for remote start and deluge valve start
• Anti-condensation heater and thermostat
• Tropicalization
• Remote alarm circuits rated 8A. 250 VAC for: Controller trouble (1 DPDT):
• Pump room alarms (1 DPDT):Controller protection level:
• IP 55 enclosure
Pressure / Event recorder:
• 15-day pressure and 15-day event recorder with RS-232 communication port for data retrieval
Power and engine connections enclosure entrance:
• Bottom gland plate
How to order:
| GFD | Negative ground | 12 or 24 VDC | Wall mounted | BCE | 10 | Options |
|---|---|---|---|---|---|---|
| GFD | N/ | 12/ | W/ | 60/ | 10/ | Options |