Standard, Listings, Approvals and Certifications
- Built to NFPA 20 (latest edition)
- Underwriters Laboratory (UL)
- UL218 - Fire pump controllers
- CSA C22.2 No. 14 Industrial Control Equipment
- FM Global - Class 1321/1323
- New York City - Accepted for use in the City of New York by the Department of Building
- Optional: CE Mark - Various EN, IEC & CEE directives and standards
Enclosure Protection Rating
Standard: NEMA 2 Assembly
Optional:
• NEMA 12 • NEMA 3 • NEMA 3R • NEMA 4 • NEMA 4X-304 sst painted • NEMA 4X-304 sst brushed finish • NEMA 4X-316 sst painted • NEMA 4X-316 sst brushed finish
|
• IP54 • IP55 • IP65 • IP66
|
Accessories • Bottom entry gland plate • Lifting Lugs • Keylock handle |
Paint Specifications • Red RAL3002 • Powder coating • Glossy textured finish |
ViZi Touch Operator Interface
- Embedded microcomputer with software PLC logic
- Expandable storage
- 4.2” color touch screen (HMI technology)
- Upgradable software
- Multi-language
Standard Features
|
AC
- 120V/1ph/60hz
- 208V to 240V/1ph/50-60hz
DC
Grounding system: Negative
Battery chargers
- Two independent fully automatic
- 10A continuous charge
- 500mA trickle charge
Readings
- Electrical readings
- Battery (x2) voltage and amperage
- Charging mode
- Pressure readings
- Cut-in cut-out and continuous system pressure
|
Alarm contacts for remote indication*
- Engine run (2)
- Common controller trouble
- Common engine trouble
- Common pump room alarm
- H-O-A in AUTO
- H-O-A in OFF or HAND
Visual and audible alarms*
- AC present
- Main switch in AUTO
- Battery #1 & #2 failure
- Charger #1 & #2 failure
- Low oil pressure
- High engine temperature
- Overspeed
- Engine run
- Fail to start
|
Operation
|
Selector Switch
- HAND-OFF-AUTO
- Behind lockable and breakable cover
Manual Start
- Crank 1 and Crank 2 start pushbuttons
- Run test pushbutton
- Deluge valve start
- Remote start from manual device
Stopping
- Manual with Stop pushbutton
- Automatic after expiration of minimum run timer
Actuation
|
Automatic Start
- Start on pressure drop
- Remote start signal from automatic device
Crank Cycle
- 6 consecutive cycle attempts
- 3 X 15s crank from battery 1 or 2 alternatively
- 15s rest in between each crank
Timers
- Field Adjustable & Visual Countdown
- Minimum run timer (off delay)
- Sequential start timer (on delay)
- Periodic test timerattempt
Mode
|
Pressure Sensing
- Pressure transducer and run test solenoid valve assembly for fresh water application externally mounted with protective cover
Pressure and Event Recorder
- Pressure readings and event recording with date stamp
- Stored in memory for lifetime of controller
- Data viewable on operator interface display screen
- Downloadable by USB port to external memory device
Audible Alarm
- 4” alarm bell - 85 dB at 10ft. (3m)
* For a complete list please see submittal packages
How to order:
| GPD | 12 or 24 VDC | 120VAC or 208 to 240VAC | options |
| GPD |
12 |
220 |
B1, C7 |