Tornatech - Fire Pump Controllers - Industrial Pump Controllers - Toll Free : 1-800-363-8448

Jockey Pump Controllers


Model JPY

Model JPY

Jockey Pump Controllers

UL CE CSA

Controller protection level:

  • Standard: NEMA - UL - CSA type 3, and 3R
  • Optional: NEMA - UL - CSA type 12 or 4 or 4X

Operational temperature limits:

  • 41°F to 122°F (5°C to 50°C)

Short circuit interrupting capacity:

  • 50 KA (RMS) at 120 V. to 480 V.
  • 30 KA (RMS) at 600 V., 7.5 HP max.
  • 18 KA (RMS) at 600 V., 20 HP max.

Manual operators (door mounted):

  • Disconnect handle and door interlock c/w padlock provision in OFF position
  • "Hand-Off-Auto" selector switch, rotary type, heavy duty

Control features:

  • Main disconnect switch
  • Wye-delta open transition motor starter HP rated
  • Thermomagnetic motor protector c/w short circuit and motor overload protection
  • Pressure switch for clean water only c/w adjustable cut-in setting and independent differential adjustment (6-250PSIG)
  • Control transformer (line voltage to 120V.)

How to order:

JPY-V/HP/Ph/Hz
JPY-208/2/3/60
Brochure
Submittal drawings


Tornatech
7075, Place Robert-Joncas # 132
Saint-Laurent (Québec)
H4M 2Z2

Printed on: Thursday, July 29, 2010
Phone: 514 334–0523
Fax: 514 334-5448
Toll free: 1 800 363-8448
E-mail: info@tornatech.com