Controller protection level:
- Standard: NEMA 2
- Optional: NEMA 12 or 4 or 4X or 3/3R
Operational temperature limits:
- 41°F to 122°F (5°C to 50°C)
Short circuit interrupting capacity:
- 50 KA (RMS) at 120 V. to 480 V.
- 30 KA (RMS) at 600 V., 7.5 HP max.
- 18 KA (RMS) at 600 V., 20 HP max.
Manual operators (door mounted):
- Disconnect handle and door interlock c/w padlock provision in OFF position
- "Hand-Off-Auto" selector switch, rotary type, heavy duty
Control features:
- Main disconnect switch
- Wye-delta open transition motor starter HP rated
- Thermomagnetic motor protector c/w short circuit and motor overload protection
- Pressure switch for clean water only c/w adjustable cut-in setting and independent differential adjustment (6-250PSIG)
- Control transformer (line voltage to 120V.)
How to order:
| JPY- | V/ | HP/ | Ph/ | Hz |
| JPY- |
208/ |
2/ |
3/ |
60 |
Brochure