Tornatech
Aller directement au contenu
May 18, 2012 - 8:29:41 EST
Toll Free 1 800 363-8448
Listen • Develop • Lead
Share |
Print

Medium voltage fire pump controller

Model MPA

Model MPA

Medium voltage fire pump controller

  • Medium Voltage
  • Micro-processor based
CE FM NFPA
UL

Controller protection level:

  • Standard NEMA - UL - type 2 
  • Optional NEMA - UL - type 4 and 4X 

Operational temperature limits:

  • 41ºF to 122ºF (5ºC to 50ºC)

Withstand rating

  • 44.7KA RMS

Enclosure Features:

  • Three compartments with individual doors for :
    Main disconnect switch
    Starter (fuses and vacuum contactor)
    Control circuit
  • Main disconnect switch compartment door is interlocked with starter compartment door
  • Power to control circuit is disconnected when main disconnect switch compartment door is opened
VoltageHPDimensions
2300V, 3ph, 50/60Hz 100 to 1500HP 90'' H x 30'' W x 28'' D
3300-4160V, 3ph, 50/60Hz 100 to 3000HP 90'' H x 30'' W x 28'' D
5000-7200V, 3ph, 50/60Hz 100 to 5000HP 90'' H x 30'' W x 28'' D

Weight: Please contact factory.