Controller protection level:
- Standard NEMA - UL - type 2
Operational temperature limits:
- 41ºF to 122ºF (5ºC to 50ºC)
Annunciator and LCD display
- Accessible without opening main door
- Normal and alternate power indication
- Transfer switch status indication
- Transfer switch bypass time delay, alarm reset and silence pushbutton
Micro-processor based logic control
- Mechanically protected and shielded
The transfer switch assembly includes:
- One Test push button to simulate a normal power failure. Pressing the Test push button for more than 3 seconds will initiate the transfer to 2nd utility power source.
The retransfer to the normal power source is initiated automatically after 5 minutes.
- Time delays:
To override momentary normal power outages before transfer to 2nd utility. Factory set at 3 seconds.
To retransfer to normal power. Instantaneous retransfer in case of alternate (emergency) power failure. (Factory set at 5 minutes.)
To allow engine generator cool-down after retransfer to normal source (if applicable). Factory set at 5 minutes.
- Voltage, frequency and phase reversal sensing:
Voltage sensing on all phases of normal power, set at 85%. A voltage below this value or phase reversal initiates transfer to 2nd utility.
2nd utility voltage and frequency sensing set at 90%. A voltage or frequency above this value initiates transfer to 2nd utility power.
Voltage sensing on all phases of normal power, set at 90%. A voltage above this value initiates retransfer to normal power.