Model GPD-FM

Diesel engine fire pump controllers

  • Designed to control Diesel Engine driven Fire Pumps
  • Built to the latest NFPA 20 Standards and FM Approved
  • Manual and Automatic Operation
  • Built in Battery Chargers
  • Pressure and event Recorder

Certifications

Our products respect all of these norms.

  • FM
  • CE

AC
•120V/1ph/60hz       
•208V to 240V/1ph/50-60hz

DC
•12VDC         
•24VDC    
     
Grounding system: Negative 

Battery chargers      
•Two independent fully automatic
•10A continuous charge
•500mA trickle charge 

Readings
•Electrical readings
   - Battery (x2) voltage and amperage
   - Charging mode
   - Pressure readings
    • Cut-in cut-out and continuous system pressure

Alarm contacts for remote indication
•Engine run
•Common controller trouble
•Common engine trouble
•Common pump room alarm (field re-assignable)
•H-O-A in OFF or HAND
•Free (field programmable)

Visual and audible alarms
•AC present
•Main switch in AUTO
•Battery  #1 & #2 failure
•Charger #1 & #2 failure
•Low oil pressure
•High engine temperature
•Overspeed
•Engine run
•Fail to start

 

DIMENSIONS AND SUBMITTAL PACKAGE
DIMENSIONS ONLY SUBMITTAL PACKAGE  
  GPDFM-DI-E   GPD-FM-SV-E