Model GPL – Limited Service Fire Pump Controllers

Model GPL – Limited Service Fire Pump Controllers

Model GPL
Limited Service Electric Fire Pump Controller

  • Designed for use with electric motor driven fire pumps.
  • Manufactured in accordance with the NFPA 20 standard and UL listed
  • ViZiTouch 7 inch Color Touch Screen Operator Interface (HMI technology)

Limitations

  • Across the line starting only
  • Horsepower rating of maximum 30hp
  • Can only be installed where acceptable by the authority having jurisdiction
  • Not accepted in FM insured property


Model GPL+ GLU
Limited Service Electric Fire Pump Controller with Automatic Power Transfer Switch

  • Required if normal utility power is not reliable
  • Housed in a barriered compartment or in a separate enclosure attached to the fire pump controller
  • Listed and Approved for fire pump service
  • Equipped with a transfer switch TEST pushbutton
Certificate Certificate Certificate

Model GPL
Limited Service Electric Fire Pump Controller

  • Designed for use with electric motor driven fire pumps.
  • Manufactured in accordance with the NFPA 20 standard and UL listed
  • ViZiTouch 7 inch Color Touch Screen Operator Interface (HMI technology)

Limitations

  • Across the line starting only
  • Horsepower rating of maximum 30hp
  • Can only be installed where acceptable by the authority having jurisdiction
  • Not accepted in FM insured property


Model GPL+ GLU
Limited Service Electric Fire Pump Controller with Automatic Power Transfer Switch

  • Required if normal utility power is not reliable
  • Housed in a barriered compartment or in a separate enclosure attached to the fire pump controller
  • Listed and Approved for fire pump service
  • Equipped with a transfer switch TEST pushbutton
  • Limitations
    • Across the line starting only
    • Horsepower rating of maximum 30hp
    • Can only be installed where acceptable by the authority having jurisdiction
    • Not accepted in FM insured property
  • Surge Suppression
  • Disconnecting means
    • Single operator for circuit breaker
    • Door interlocked in the ON position
  • Suitable as service entrance equipment
  • Emergency start handle
  • Readings
    • Voltage and amperage display
    • Cut-in, cut-out and continuous system pressure
  • Visual indications:
    • Standard Conditions
    • Alarm Conditions
    • Color coded for criticalness
  • Remote Alarms (SPDT-8A-250V.AC)
    • Power available
    • Phase reversal
    • Motor run
    • Common pump room alarm
    • Common Motor trouble
  • Built to NFPA 20 (latest edition)
  • Underwriters Laboratory (UL)
    • UL218 – Fire pump controllers
    • UL 1008 – Automatic power transfer switches for fire pump controllers
    • CSA C22.2 No. 14 Industrial Control Equipment
  • New York City – Accepted for use in the City of New York by the Department of Buildings

ViZitouch V2 Operator Interface

  • 7” color touch screen (HMI technology)
  • Embedded microcomputer with software PLC logic
  • Expandable storage
  • Multi-language
  • Upgradable software  
  • Enclosure Protection Rating
    • Standard: NEMA 2 Assembly
    • Optional:
      • NEMA 12
      • NEMA 3
      • NEMA 3R
      • NEMA 4
      • NEMA 4X-304 sst painted
      • NEMA 4X-304 sst brushed finish
      • NEMA 4X-316 sst painted
      • NEMA 4X-316 sst brushed finish
  • Accessories
    • Keylock handle
  • Paint Specifications
    • Red RAL3002
    • Powder coating
    • Glossy textured finish 

Model GPL+ GLU- Automatic Power Transfer switch
Limited Service Electric Fire Pump Controller with Automatic Power Transfer Switch

  • Surge suppression
  • Disconnecting means
    • Single operator for circuit breaker
    • Door interlocked in the ON position
  • Visual indications
    • Alternate (emergency)  isolating switch in the OFF position
    • Alternate (emergency) voltage phase to phase
    • Transfer switch in normal position
    • Transfer switch in Alternate (emergency) position
  • Transfer switch test pushbutton
  • Bypass for re-transfer and generator shutdown
  • Electrically operated and mechanically held  in the normal or alternate position
  • Provision for manual operation
  • Time Delays
    • Momentary normal power outage override (factory set at 3 sec – field adjustable 1 to 3 sec)
    • Alternate (emergency) power available delay (factory set at 3 sec – field adjustable 1 to 3 sec)
    • Transfer trouble delay (factory set at 20 sec – field adjustable 1 to 60 sec)
    • Retransfer to normal (factory set at 5 min – field adjustable 1 to 20 min)
    • Generator cooldown (factory set at 5 min – field adjustable 1 to 20 min)
  • Voltage sensing
    • Transfer to alternate (normal power dropout) 85% of nominal – field adjustable 0 to 100%
    • Phase reversal transfer to alternate
    • Retransfer to normal (normal power pickup) 90% of nominal – field adjustable 0 to 100%
  • Remote alarm contacts
  • Generator start connection

(Click to expand)

 

certificate certificate certificate
Available Models
Click here for Specifications, Submittal Packages, etc.