VPx Series – Variable Speed Electric Fire Pump Controllers (VFD)
- Designed to maintain a constant pressure output from the fire pump
- A variable frequency drive (VFD) is used to vary the speed of the fire pump’s electric motor, taking into consideration the constant pressure output required.
- The variable speed drive will ramp up the electric motor speed to obtain the desired constant pressure output in maximum 10 seconds.
- Designed to maintain a constant pressure output from the fire pump
- A variable frequency drive (VFD) is used to vary the speed of the fire pump’s electric motor, taking into consideration the constant pressure output required.
- The variable speed drive will ramp up the electric motor speed to obtain the desired constant pressure output in maximum 10 seconds.
- Single operator for both isolating switch and circuit breaker
- Surge arrestor
- Locked rotor protector
- Line reactor 5%
- Mode Selector Switch
- VFD
- Bypass
- VFD Fault and VFD Bypass visual indication
- Start and stop pushbuttons
- Run test push button
- Emergency start handle
- Phase reversal indication
- Remote start / deluge valve start provision
- Pressure transducers and run test solenoid valve externally mounted
- Audible alarm
- Alarm contacts for remote indication
- Available with automatic transfer switch
- Built to NFPA 20 (latest edition)
- Underwriters Laboratory (UL)
- UL218 – Fire pump controllers
- FM Global – Class 1321/1323
- ViZiTouch V2.1 operator interface
- Voltage and amperage display
- Constant pressure output set-point display
- System pressure, cut-in and cut-out display
- VFD Hertz display
- Pressure and event recorder
- NEMA 12 ventilated assembly
- Conductor entry gland plates
- Lifting lugs
- Doors with keylock handle and quarter-turn latches
- Red RAL3002
- Powder coated / glossy textured finish
- Surge suppression
- Disconnecting means
- Single operator for both isolating switch and circuit breaker
- Door interlocked in the ON position
- Locked rotor protector
- Visual indications
- Alternate (emergency) isolating switch in the OFF position
- Alternate (emergency) voltage phase to phase
- Transfer switch in normal position
- Transfer switch in Alternate (emergency) position
- Transfer switch test pushbutton
- Bypass for re-transfer and generator shutdown
- Electrically operated and mechanically held in the normal or alternate position
- Provision for manual operation
Time delays:
- To override momentary normal power outages before transfer to the alternate (emergency) power source. Factory set at 3 seconds.
- To retransfer to normal power. Instantaneous retransfer in case of alternate (emergency) power failure. (Factory set at 5 minutes.)
- To allow engine generator cool-down after retransfer to normal source. Factory set at 5 minutes.
Voltage, frequency and phase reversal sensing:
- Voltage sensing on all phases of normal power, set at 85%. A voltage below this value or phase reversal initiates transfer to the alternate (emergency) power source.
- Alternate (emergency) power source voltage and frequency sensing set at 90%. A voltage or frequency above this value initiates transfer to the alternate (emergency) power source.
- Voltage sensing on all phases of normal power, set at 90%. A voltage above this value initiates retransfer to normal power.
Remote alarm contacts
- Emergency power isolating switch in the OFF position
- Transfer switch in normal position
- Transfer switch in emergency position
Generator start connection