Model GPD-FM – Diesel Engine Fire Pump Controllers
- Designed to control Diesel Engine driven Fire Pumps
- Built to the latest NFPA 20 Standards and FM Approved
- Manual and Automatic Operation
- Built in Battery Chargers
- Pressure and event Recorder


- Designed to control Diesel Engine driven Fire Pumps
- Built to the latest NFPA 20 Standards and FM Approved
- Manual and Automatic Operation
- Built in Battery Chargers
- Pressure and event Recorder
AC
•120V/1ph/60hz
•208V to 240V/1ph/50-60hz
DC
•12VDC
•24VDC
Grounding system: Negative
Battery chargers
•Two independent fully automatic
•10A continuous charge
•500mA trickle charge
Readings
•Electrical readings
– Battery (x2) voltage and amperage
– Charging mode
– Pressure readings
• Cut-in cut-out and continuous system pressure
Alarm contacts for remote indication
•Engine run
•Common controller trouble
•Common engine trouble
•Common pump room alarm (field re-assignable)
•H-O-A in OFF or HAND
•Free (field programmable)
Visual and audible alarms
•AC present
•Main switch in AUTO
•Battery #1 & #2 failure
•Charger #1 & #2 failure
•Low oil pressure
•High engine temperature
•Overspeed
•Engine run
•Fail to start
• Built to NFPA 20 (latest edition)
• FM Global – Class 1321/1323
• CE Mark – Various EN, IEC & CEE directives and standards
ViZiTouch Operator Interface
• Embedded microcomputer with software PLC logic
• Expandable storage
• 4.2” color touch screen (HMI technology)
• Upgradable software
• Multi-language
Enclosure
Protection Rating
Standard: IP55
Accessories
• Bottom entry gland plate
• Lifting Lugs
• Keylock handle
Paint Specifications
• Red RAL3002
• Powder coating
• Glossy textured finish