Model GPD-FM – Diesel Engine Fire Pump Controllers

Manufactured in Belgium for the European markets

Model GPD-FM – Diesel Engine Fire Pump Controllers

Downloadables Manual
Brochure
  • Designed to control Diesel Engine driven Fire Pumps
  • Built to the latest NFPA 20 Standards and FM Approved
  • Manual and Automatic Operation
  • Built in Battery Chargers
  • Pressure and event Recorder
Certificate Certificate
  • Designed to control Diesel Engine driven Fire Pumps
  • Built to the latest NFPA 20 Standards and FM Approved
  • Manual and Automatic Operation
  • Built in Battery Chargers
  • Pressure and event Recorder

AC
•120V/1ph/60hz
•208V to 240V/1ph/50-60hz

DC
•12VDC
•24VDC

Grounding system: Negative

Battery chargers
•Two independent fully automatic
•10A continuous charge
•500mA trickle charge

Readings
•Electrical readings
– Battery (x2) voltage and amperage
– Charging mode
– Pressure readings
• Cut-in cut-out and continuous system pressure

Alarm contacts for remote indication
•Engine run
•Common controller trouble
•Common engine trouble
•Common pump room alarm (field re-assignable)
•H-O-A in OFF or HAND
•Free (field programmable)

Visual and audible alarms
•AC present
•Main switch in AUTO
•Battery  #1 & #2 failure
•Charger #1 & #2 failure
•Low oil pressure
•High engine temperature
•Overspeed
•Engine run
•Fail to start

• Built to NFPA 20 (latest edition)
• FM Global – Class 1321/1323
• CE Mark – Various EN, IEC & CEE directives and standards

ViZiTouch Operator Interface
• Embedded microcomputer with software PLC logic
• Expandable storage
• 4.2” color touch screen (HMI technology)
• Upgradable software
• Multi-language

Enclosure

Protection Rating
Standard: IP55

Accessories
• Bottom entry gland plate
• Lifting Lugs
• Keylock handle

Paint Specifications