Model GPL – Limited Service Electric Additive (Foam) Pump Controllers
Additive (Foam) Pump Controllers are typically designed for use in buildings where flammable or combustible liquids are present such as aircraft hangers, petro-chemical and hazardous waste facilities.
Model GPL – Full Voltage Across the Line Start
Transfer switch available.
Choose one of the following configurations:
- A8 – Additive (Foam) pump controller / non pressure actuated without pressure transducer and run test solenoid valve
- A8A – Additive (Foam) pump controller with pressure transducer and run test solenoid valve
Add any of the following options if required:
- D40 – Dump valve circuitry, 24VDC Max2A
- Cx79 – Low foam additive level complete with visual indication and alarm contact (DPDT)
- Cx081- Provision for proof pressure switch for low additive pressure complete with visual indication and alarm contact. (Proof pressure switch provided by others.)
Additive (Foam) Pump Controllers are typically designed for use in buildings where flammable or combustible liquids are present such as aircraft hangers, petro-chemical and hazardous waste facilities.
Model GPL – Full Voltage Across the Line Start
Transfer switch available.
Choose one of the following configurations:
- A8 – Additive (Foam) pump controller / non pressure actuated without pressure transducer and run test solenoid valve
- A8A – Additive (Foam) pump controller with pressure transducer and run test solenoid valve
Add any of the following options if required:
- D40 – Dump valve circuitry, 24VDC Max2A
- Cx79 – Low foam additive level complete with visual indication and alarm contact (DPDT)
- Cx081- Provision for proof pressure switch for low additive pressure complete with visual indication and alarm contact. (Proof pressure switch provided by others.)
- Designed for use with electric motor drivenfire pumps.
- Manufactured in accordance with the NFPA 20 standard and UL listed
- ViZiTouch 7 inch ColorTouch Screen Operator Interface (HMI technology)
Limitations
- Across the line starting only
- Horsepower rating of maximum 30hp
- Can only be installed where acceptable by the authority having jurisdiction
- Not accepted in FM insured property
- Limitations
- Across the line starting only
- Horsepower rating of maximum 30hp
- Can only be installed where acceptable by the authority having jurisdiction
- Not accepted in FM insured property
- Surge Suppression
- Disconnecting means
- Single operator for circuit breaker
- Door interlocked in the ON position
- Suitable as service entrance equipment
- Emergency start handle
- Readings
- Voltage and amperage display
- Cut-in, cut-out and continuous system pressure
- Visual indications:
- Standard Conditions
- Alarm Conditions
- Color coded for criticalness
- Remote Alarms (SPDT-8A-250V.AC)
- Power available
- Phase reversal
- Motor run
- Common pump room alarm
- Common Motor trouble
- Built to NFPA 20 (latest edition)
- Underwriters Laboratory (UL)
- UL218 – Fire pump controllers
- UL 1008 – Automatic power transfer switches for fire pump controllers
- New York City – Accepted for use in the City of New York by the Department of Buildings
ViZitouch V2 Operator Interface
- 7” color touch screen (HMI technology)
- Embedded microcomputer with software PLC logic
- Expandable storage
- Multi-language
- Upgradable software
- Enclosure Protection Rating
- Standard: NEMA 2 Assembly
- Optional:
- NEMA 12
- NEMA 3
- NEMA 3R
- NEMA 4
- NEMA 4X-304 sst painted
- NEMA 4X-304 sst brushed finish
- NEMA 4X-316 sst painted
- NEMA 4X-316 sst brushed finish
- Accessories
Keylock handle
- Paint Specifications
- Red RAL3002
- Powder coating
- Glossy textured finish