Manufactured in Canada for all marketsManufactured in Belgium for the European marketsManufactured in Dubai for the Middle East and Asia markets
Model GPD – Diesel Engine Fire Pump Controllers
Diesel Engine Fire Pump Controllers
- Designed to control Diesel Engine driven Fire Pumps
- Manufactured in accordance with the NFPA 20 standard, UL listed and FM Approved
- Manual and Automatic Operation
- Built in Battery Chargers
- Pressure and event Recorder
Diesel Engine Fire Pump Controllers
- Designed to control Diesel Engine driven Fire Pumps
- Manufactured in accordance with the NFPA 20 standard, UL listed and FM Approved
- Manual and Automatic Operation
- Built in Battery Chargers
- Pressure and event Recorder
AC
- 120V/1ph/50-60hz
- 208V to 240V/1ph/50-60hz
DC
- 12VDC
- 24VDC
Grounding system: Negative
Battery chargers
- Two independent fully automatic
- 10A continuous charge
- 500mA trickle charge
- Electrical readings
- Battery (x2) voltage and amperage
- Charging mode
- Pressure readings
- Cut-in cut-out and continuous system pressure
Alarm contacts for remote indication* (DPDT-8A-250V.AC)
- Engine run
- Common controller trouble
- Common engine trouble
- Common pump room alarm (field re-assignable)
- H-O-A in OFF or HAND
- Free (field programmable)
Visual and audible alarms*
- AC present
- Main switch in AUTO
- Battery #1 & #2 failure
- Charger #1 & #2 failure
- Low oil pressure
- High engine temperature
- Overspeed
- Engine run
- Fail to start
* For a complete list please see submittal packages
- Built to NFPA 20
- Underwriters Laboratory (UL)
- UL218 – Fire pump controllers
- FM Global – Class 1321/1323
- New York City – Accepted for use in the City of New York by the Department of Building
- Optional: CE Mark – Various EN, IEC & CEE directives and standards
ViZiTouch 2.1 Operator Interface
- Embedded microcomputer with software PLC logic
- Expandable storage
- 7” color touch screen (HMI technology)
- Upgradable software
- Multi-language
- Standard: NEMA 2 Assembly
- Optional:
- NEMA 12
- NEMA 3
- NEMA 3R
- NEMA 4
- NEMA 4X-304 sst painted
- NEMA 4X-304 sst brushed finish
- NEMA 4X-316 sst painted
- NEMA 4X-316 sst brushed finish
- IP54
- IP55
- IP65
- IP66
- Accessories
- Bottom entry gland plate
- Keylock handle
- Paint Specifications
- Red RAL3002
- Powder coating
- Glossy textured finish